Ultra Pressure Logo

Ultra Pressure Components, Inc.
17411 West Strack Drive
Spring, Texas 77379
Tel: (713)937-0017
Toll Free: (833)-HIGHPSI
Email: sales@ultrapressurecomponents.com

 

 

Superlok I-Fitting & Standard Tube Fitting Installation Procedures

Superlok I-Fitting Installation Procedure

install_1

Out of box state. Red pop off ring attached and secondary blue inspection band underdeath

installation 2

Insert tube into the fitting until it stops. Hand tighten nut firmly.

installaton 3

Insert wrench on wrench flats of both nuts. Turn approximately 1-1/4 turns until red ring seperates and pops off. Visually double check gap by blue band.

  • Reduces installation time
  • No additional inspection gauge required
  • Secondary inspection gauge built in
  • Saves time and money - End leaks and wasted fittings

Superlok Standard Tube Fitting Installation Procedure

1. Installation under 1 inch or 25mm

Superlok Tube Fittings shall be delivered to the customer completely assembled and ready for installation. Turning the nut to the finger tight position is the only requirement before starting the installation. Fittings should not be disassembled before installation to maintain cleanliness and prevent unwanted foreign material from entering the system. Care in the proper selection of tubing

Step 1

Insert the tubing into the Superlok Tube fitting making sure the tubing is bottomed out and is in complete contact with the shoulder of the fitting. Also, the nut should be in the finger-tight position at this time.

Step 2

Before tightening, mark the Superlok nut at the 6 o’clock position.

Step 3

Hold the fitting body safely with a back-up wrench and tighten the nut 1-1/4 turns until your mark reaches the 9 o’clock position.
Note: For 1/16”, 1/8” and 3/16”, 2, 3 and 4 mm tube fittings, tighten the nut 3/4 of a turn to the 3 o’clock position.